| ASTM C 612 |
Mineral Fiber Block and Board Thermal Insulation |
Type IVB, Complies |
| CAN/CGSB 51.10-92 |
Mineral Fibre Board Thermal Insulation |
Type 1, Class 4 |
| MEA Approval |
New York City Approval |
332-97-M |
| City Of Los Angeles Approval |
|
R 25444 |
| UL Design Nos. |
CW-S-1008,1009,1012,1014, 2004, 2005, 2007,2009, Hour 2010, 2011, 2012, 2015, 2016,2017,2018, 2019, 2020, 2024, 2026, 2027, 2028, 2029, 2030, 2031, 2032, 2037, 2038, 2042, 2043, 2053, 2054, 2055, 2056, 2057 CW-D-2007, 2014, 2015, 2016, 2017, 2018, 2019, 2025, 2026, 2027, 2028, 2029, 2030, 2031, 2032, 2033, 2034, 2035 |
2 Hour Integrity Rating |
|
|
|
|
| ASTM E 136 |
Behavior of Materials at 1382ºF(750ºC) |
Non-Combustible |
| CAN4S114 |
Test for Non-Combustibility |
Non-Combustible |
| ASTM E 84(UL 723) |
Surface Burning Characteristics |
Flame Spread = 0 Smoke Developed = 0 |
| CAN/ULC S102 |
Surface Burning Characteristics |
Flame Spread = 0 Smoke Developed = 0 |
|
|
|
|
| ASTM C 411 |
Hot Surface Performance |
In Compliance with ASTM C612 @ 1200ºF (650ºC) |
|
|
|
|
| ASTM C 356 |
Linear Shrinkage |
< 1 % @ 1200ºF (650ºC) |
|
|
|
|
| ASTM C 1104 |
Moisture Sorption |
< 0.04% |
|
|
|
|
| ASTM C 665 |
Corrosiveness to Steel |
Passed |
| ASTM C 795* |
Stainless Steel Stress Corrosion Specification as per Test Methods C871 and C692: U.S. Nuclear Regulatory Commission, Reg. Guide #1.36: U.S. Military Specifications MIL-l-24244 (all versions including B and C) |
Conforms |
*Provisions for lot testing may be required, consult manufacturer.
|
|
|
|
| ASTM C 423 |
| CO-EFFICIENTS AT FREQUENCIES |
| Thickness |
125 |
250 |
500 |
1000 |
2000 |
4000 |
NRC |
|
Hz |
Hz |
Hz |
Hz |
Hz |
Hz |
|
| 1.5" |
0.17 |
0.58 |
1.06 |
1.07 |
1 |
0.99 |
0.95 |
| 2.0" |
0.39 |
0.84 |
1.08 |
1.01 |
1.02 |
1.01 |
1 |
| 3.0" |
0.68 |
0.92 |
1.08 |
1.03 |
1.03 |
1.03 |
1.1 |
| 4.0" |
1 |
0.95 |
1.06 |
1.04 |
1.06 |
1.08 |
1.05 |
|
|
|
|
| ASTM C 518 (C 177) |
R-value/inch @ 75ºF |
4.2 hr.ft².F/Btu |
|
RSI value/25.4 mm @ 24ºC |
0.75 m²K/W |
|
|
|
|